Mechanical pressure and temperature switches perform sensitive tasks in safety-relevant applications, e.g. monitoring limit values. Their functional safety must be guaranteed accordingly. That is always the case if the instruments fulfil certain requirements of the corresponding safety integrity level (SIL) relative to the IEC 61508 standard. WIKA switches have been issued SIL approval due to their proven operational reliability.
Examples of WIKA switches whose functional safety is SIL-certified: a concise temperature switch with Ex d flameproof enclosure (model TCA; left), a Bourdon tube pressure switch (model BA/BAX; top right) and a miniature pressure switch (model PXS; bottom right).
Hazards to people, the environment and the plant that can emanate from critical processes must therefore be reduced to a satisfactory minimum. IEC 61508 supplies the necessary specifications for this. These are defined in various safety integrity levels, SIL 1 to 4.
The standard places equal responsibility on the responsible process developers and the manufacturers of the necessary components. For every instrument, it defines limit values for the probability of failure of a safety-relevant function. As well, it provides criteria for the possibility of controlling and avoiding systematic errors.
Once the topic of ?functional safety? is discussed in expert groups regarding the SIL approval, it is mainly concerning electrical systems. However, numerous mechanical components may also be integrated within safety-relevant applications. Included in these are measuring instruments that do not want external power and for that reason work reliably, even yet in the event of an electrical failure. A SIL approval for these does mean a clear statement on functional safety. Regarding mechanical parts, it is primarily a question of the effects of aging and wear.
Individually installed: SIL 2, combined redundantly: SIL 3
The SIL certificate for WIKA?s pressure and temperature switches was issued in 2019 by exida, a globally recognised testing company. In accordance with its assessment, the instruments, when installed individually, meet up with the requirements of SIL 2, and in redundant combination, they even meet those of the particular level SIL 3.
หลักการทำงานของเกจ์วัดแก๊ส to assessment
As well as the actual classification, the certificate for the WIKA switches also includes the addition ?route 2H?. In principle, you can find two ways to reach a SIL assessment: ?Route 1H? states that the instruments or components in question have already been developed and manufactured in accordance with the respective SIL specifications. ?Route 2H?, alternatively, confirms that the assessment was additionally predicated on their operational reliability, as in the case of WIKA switches. The certified error rate is calculated from data collected during used in a credit card applicatoin in the field and transmitted to exida. The SIL assessment of functional safety is thus carried out on a realistic basis: For each component of a device, at the very least 100 million operating hours will need to have been proven.
Empirical values in a database
The SIL assessment relative to route 2H refers to the empirical values from field use, which are stored within an exida database. There, specific operating conditions such as for example temperature, vibration etc. are considered.
Note
Detailed information on switches with SIL certificate ? pressure switches of the M, B, A, D, PC and PX series and temperature switches of the T series ? are available on the WIKA website. The approval certificate is also available as a PDF file there. Assuming you have any further questions, your contact will gladly assist you to.
Also read our articles
SIL pressure switch: Safety in tyre manufacturing